Schneider Electric A9F85125 Miniature circuit breaker iC60H, 1P 25A D-curve. The Schneider Electric A9F85125 is a robust Acti9 iC60H Miniature Circuit Breaker (MCB) designed for reliable protection in final distribution circuits. This essential electrical component features a 1P pole description, a 25A rated current, and a D-curve tripping characteristic, ensuring optimal safety against overloads and short circuits. It boasts a substantial breaking capacity of 10000 A (IEC/EN 60898-1) at 230 V AC and 15 kA (IEC/EN 60947-2) at 220-240 V AC, making it suitable for demanding applications. The thermal-magnetic trip unit provides dependable performance across both AC and DC network types, supporting a wide operational voltage range, including the common 220-240 V AC found in the region. Designed for easy integration, it features clip-on mounting for 35 mm DIN rails and an IP20 degree of protection. This versatile Schneider Electric A9F85125 MCB is indispensable for electrical infrastructure in various demanding sectors across Egypt and the Gulf, such as cement production, oil and gas operations, water treatment, food and beverage processing, textile manufacturing, and critical building services. For detailed technical specifications or to request a quote, please contact us.

Details

Related Schneider Electric parts

Request a quote for A9F85125

Specifications

Curve code
D
Net weight
0.215 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Poles description
1P
Tightening torque
2 N.M top or bottom
[In] rated current
25 A
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Wire stripping length
14 Mm for top or bottom connection
Dimensions (H x W x D)
85 Mm x 18 Mm x 78.5 Mm
Connections - terminals
Single terminal (top or bottom), for 1 cable(s), 1…25 mm² rigid copper, 1…16 mm² flexible copper
IP degree of protection
IP20
Manufacturer part number
A9F85125
[Ue] rated operational voltage
12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V DC, 60...72 V DC
Breaking capacity (IEC/EN 60898-1)
10000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
15 KA Icu at 220-240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation