A9V41240

Schneider Electric A9V41240 — Residual Current Device

Schneider Electric A9V41240 Acti9 Vigi iC60 2-pole 40 A 30 mA type AC add-on residual current device. The Schneider Electric A9V41240 is an Acti9 Vigi iC60 add-on residual current device, two poles, 40 A, 30 mA type AC instantaneous, for 230...240 V AC. It bolts directly onto an Acti9 iC60 or Reflex iC60 miniature circuit breaker by screws, converting a plain MCB into a combined overcurrent and earth-leakage protection assembly without changing the board layout. The A9V41240 uses voltage-independent tripping to EN/IEC 61009-1 and 61009-2-1, with 500 V AC rated insulation voltage, 6 kV impulse withstand and 250 A 8/20 microsecond surge immunity. It clips to DIN rail, measures 91 x 72 x 73.5 mm across four 9 mm pitches, accepts 1...35 mm2 rigid conductors at 3.5 N.m and is IP20 rated for -5 to 60 degrees C. It is widely used to retrofit earth-leakage protection to existing iC60 boards in hotels, food plants, water treatment and facilities maintenance across Egypt and the Gulf.

Details

Related Schneider Electric parts

Request a quote for A9V41240

Specifications

Range
Acti9
Standards
EN/IEC 61009-1, EN/IEC 61009-2-1
Net weight
0.165 kg
9 mm pitches
4
Product name
Acti9 Vigi iC60
Mounting mode
Clip-on, DIN rail
Local signalling
Trip indicator
Device short name
Vigi iC60
Network frequency
50/60 Hz
Poles description
2P
Tightening torque
3.5 N.m bottom
[In] rated current
40 A
Range compatibility
Acti9 iC60, Acti9 Reflex iC60
Dimensions (H x W x D)
91 mm x 72 mm x 73.5 mm
Connections - terminals
Tunnel type terminal downside, 1...35 mm2 rigid; 1...25 mm2 flexible
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9V41240
Earth-leakage sensitivity
30 mA
Product or component type
Add-on residual current device
Electrical connection to MCB
By screws
Electromagnetic compatibility
8/20 microsecond impulse withstand, 250 A conforming to IEC 61009-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to IEC 60947-2
Earth-leakage protection class
Type AC
[Ue] rated operational voltage
230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1 and EN/IEC 61009-2-1
Earth-leakage protection time delay
Instantaneous
Residual current tripping technology
Voltage independent
Ambient air temperature for operation
-5...60 degrees C
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2

Product documentation

View manufacturer document (PDF)