A9K24120

Schneider Electric A9K24120 — Miniature Circuit Breaker

Schneider Electric A9K24120 Acti9 iK60N 1-pole 20 A C-curve miniature circuit breaker, 6 kA. The Schneider Electric A9K24120 is an Acti9 iK60N miniature circuit breaker, one pole, 20 A rated at 30 degrees C, C tripping curve, for 230 V AC final circuits. The iK60N is the cost-optimised Acti9 MCB for residential and light commercial distribution, providing thermal-magnetic overload and short-circuit protection with 6000 A Icn to EN/IEC 60898-1 and an Ics equal to 100 % of Icn, current limitation class 3, magnetic tripping between 5 and 10 x In, 440 V AC rated insulation voltage and 4 kV impulse withstand. The A9K24120 clips onto 35 mm DIN rail, is 18 mm wide over two 9 mm pitches, has tunnel terminals for 1...25 mm2 rigid conductors at 2 N.m, a padlocking device and IP20 protection from -25 to 60 degrees C. It suits socket, small-power and lighting circuits in apartment blocks, hotels and light facilities in Egypt and the Gulf.

Details

Related Schneider Electric parts

Request a quote for A9K24120

Specifications

Range
Acti9
Standards
EN/IEC 60898-1
Curve code
C
Net weight
100 g
9 mm pitches
2
Product name
Acti9 iK60
Mounting mode
Clip-on, 35 mm DIN rail
Limitation class
3 conforming to EN/IEC 60898-1
Breaking capacity
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Device short name
iK60N
Network frequency
50/60 Hz
Poles description
1P
Tightening torque
2 N.m top or bottom
[In] rated current
20 A at 30 degrees C
Trip unit technology
Thermal-magnetic
Dimensions (H x W x D)
85 mm x 18 mm x 78.5 mm
Connections - terminals
Tunnel type terminal (top or bottom), 1...25 mm2 rigid; 1...16 mm2 flexible
IP degree of protection
IP20 conforming to IEC 60529
Magnetic tripping limit
5...10 x In
Manufacturer part number
A9K24120
Number of protected poles
1
Suitability for isolation
Yes conforming to EN/IEC 60898-1
[Ui] rated insulation voltage
440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ue] rated operational voltage
230 V AC 50/60 Hz
Mechanical / electrical durability
20000 cycles / 10000 cycles
Ambient air temperature for operation
-25...60 degrees C
[Ics] rated service breaking capacity
6000 A (100 % x Icn) at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60898-1

Product documentation

View manufacturer document (PDF)