Schneider Electric GV2L08 — Motor Circuit Breaker

Schneider Electric GV2L08 TeSys Deca GV2L motor circuit breaker 3P 4A magnetic rotary handle screw clamp. The Schneider Electric GV2L08 is a robust 3-pole motor circuit breaker from the acclaimed TeSys Deca range, engineered for reliable motor protection in demanding industrial environments. This magnetic circuit breaker, with its 4 A rated current and a substantial 74 A magnetic tripping current, is designed to safeguard motors against overloads and short circuits. Featuring a user-friendly rotary handle for control and secure screw clamp terminals for robust connections, it simplifies installation and maintenance. With a high breaking capacity of 100 kA Icu at 400/415 V AC and suitable for motors up to 3 KW at 690 V AC, the GV2L08 offers versatile protection across various power systems. Its compact design (45x89x97 mm) allows for flexible mounting on 35 mm DIN rails or directly to panels, making it adaptable to diverse enclosure setups. The IP20 degree of protection ensures suitability for typical industrial applications, from water treatment and oil & gas facilities to cement plants, food & beverage processing, and textiles across Egypt and the Gulf region. Ensure uninterrupted operation and extend the lifespan of your critical motor assets.

Details

Related Schneider Electric parts

Request a quote for GV2L08

Specifications

Depth
97 Mm
Width
45 Mm
Height
89 Mm
Net weight
0.33 Kg
Fixing mode
35 mm symmetrical DIN rail: clipped, Panel: screwed (with 2 x M4 screws)
Control type
Rotary handle
Motor power kW
1.1 KW at 400/415 V AC 50/60 Hz, 1.5 KW at 400/415 V AC 50/60 Hz, 3 KW at 690 V AC 50/60 Hz
Breaking capacity
100 KA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 4 KA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Poles description
3P
[In] rated current
4 A
Trip unit technology
Magnetic
Product certifications
CCC, UL, CSA, EAC, LROS (Lloyds register of shipping)
Connections - terminals
Power circuit: screw clamp terminal
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
GV2L08
Magnetic tripping current
74 A
Suitability for isolation
Yes conforming to IEC 60947-1
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Ambient air temperature for operation
-20…60 °C

Product documentation

View manufacturer document (PDF)