A9F75410

Schneider Electric A9F75410 — Miniature Circuit Breaker

Schneider Electric A9F75410 Acti9 iC60N Miniature Circuit Breaker 4P 10A D-Curve. The Schneider Electric A9F75410 Acti9 iC60N Miniature Circuit Breaker (MCB) is engineered for reliable protection of final distribution circuits. This 4-pole, 10A MCB features a D-curve thermal-magnetic trip unit, designed to safeguard electrical installations against overcurrents and short circuits in both AC and DC networks operating at 50/60 Hz. It offers robust breaking capacities, including 10 kA Icu at 380-415 V AC (conforming to EN/IEC 60947-2) and 6000 A Icn at 400 V AC (conforming to EN/IEC 60898-1), ensuring high performance under fault conditions. The Acti9 iC60N is suitable for isolation, boasting an IP20 degree of protection, and mounts easily on a 35 mm DIN rail. Its versatility makes it an indispensable component in critical infrastructure and industrial applications across Egypt and the Gulf, such as power distribution in cement plants, oil and gas facilities, water treatment plants, food and beverage manufacturing, and large commercial building services.

Details

Related Schneider Electric parts

Request a quote for A9F75410

Specifications

Depth
78.5 mm
Width
72 mm
Height
85 mm
Curve code
D
Net weight
0.5 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
4P
Tightening torque
2 N.M top or bottom
[In] rated current
10 A
Trip unit technology
Thermal-magnetic
Connections - terminals
Single terminal (top or bottom), for 1 cable(s), 1…25 mm² rigid, copper; Single terminal (top or bottom), for 1 cable(s), 1…16 mm² flexible, copper; Single terminal (top or bottom), for 1 cable(s), 1…16 mm² flexible with ferrule, copper
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F75410
Suitability for isolation
Yes
[Ue] rated operational voltage
12...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, <= 250 V DC
Breaking capacity (EN/IEC 60898-1)
6000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (EN/IEC 60947-2)
10 kA Icu at 380...415 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)