A9F77132

Schneider Electric A9F77132 — MCB Acti9 iC60N 1P 32A C-curve

Schneider Electric A9F77132 MCB Acti9 iC60N 1P 32A C-curve. Ensure robust and reliable protection for your electrical installations with the Schneider Electric Acti9 iC60N Miniature Circuit Breaker, part number A9F77132. This high-performance 1-pole, 32A C-curve MCB is engineered for final distribution circuits, offering superior protection against overcurrents and short-circuits in both AC and DC networks. It supports a wide range of operational voltages including 220-240 V AC 50/60 Hz, making it ideal for the electrical grids prevalent across Egypt and the Gulf region. Featuring a formidable breaking capacity of 6000 A (IEC/EN 60898-1) at 230V AC and 10 kA (IEC/EN 60947-2) at 220-240V AC, the A9F77132 guarantees safety and continuity of service. Its thermal-magnetic trip unit and DIN-rail mounting simplify installation in diverse environments. Perfect for applications in building services, water treatment, light industrial machinery, and general distribution panels within sectors like cement, food and beverage, and oil & gas. For superior circuit protection, request a quote for this essential Schneider Electric component today.

Details

Related Schneider Electric parts

Request a quote for A9F77132

Specifications

Depth
78.5 Mm
Width
18 Mm
Height
85 Mm
Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
C
Net weight
0.215 Kg
Network type
DC, AC
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
1P
[In] rated current
32 A
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F77132
Suitability for isolation
Yes
[Ue] rated operational voltage
12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V DC, 60...72 V DC
Connections - terminals (rigid)
Single terminal (top or bottom), for 1 cable(s), 1…35 mm², rigid, copper
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 220...240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)