LC1DWK12G7

Schneider Electric LC1DWK12G7 — Capacitor duty contactor

Schneider Electric LC1DWK12G7 Capacitor contactor, Tesys Deca, 63kVAR at 400/415V 50Hz, 120V AC 50/60Hz coil, screw clamp terminals. TeSys Deca contactor, 3 poles (3NO), for switching 3-phase capacitor banks up to 63kVAR@400V 50Hz (104kVAR@690V). It provides a 120V 50/60Hz AC coil, 1NO+2NC instantaneous auxiliary contacts, with front mounted early make poles and pre-wired damping resistors for current limitation. For operating rates until 240 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA) and compliant with shunt capacitors standard IEC 60831, Green Premium product (RoHS/REACh). This capacitor duty contactor supports industrial motor starters, process equipment, pumps, compressors, HVAC installations and heavy-duty electrical panels. Official Schneider characteristics include Range: TeSys; Product name: TeSys LC1D.K TeSys Deca; Product or component type: Capacitor duty contactor; Device short name: LC1DWK; Device application: Control; Contactor application: Power factor correction; Utilisation category: AC-6b; Poles description: 3P.

Details

Related Schneider Electric parts

Request a quote for LC1DWK12G7

Specifications

Range
TeSys
Product name
TeSys LC1D.K TeSys Deca
Device short name
LC1DWK
Poles description
3P
Device application
Control
Control circuit type
AC at 50/60 Hz
Utilisation category
AC-6b
Contactor application
Power factor correction
Electrical durability
300000 cycles at Ue 400 V 200000 cycles at Ue 690 V
Reactive power rating
35 kvar at 230 V AC 50 Hz 60 °C 63 kvar at 400 V AC 50 Hz 60 °C 67 kvar at 440 V AC 50 Hz 60 °C 104 kvar at 690 V AC 50 Hz 60 °C 30 kvar at 230 V AC 60 Hz 60 °C 60 kvar at 460 V AC 60 Hz 60 °C 80 kvar at 575 V AC 60 Hz 60 °C
Manufacturer part number
LC1DWK12G7
Device location in system
Inside delta interruption Line interruption
Product or component type
Capacitor duty contactor
[Uc] control circuit voltage
120 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 2 NC instantaneous
[Ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
power pole contact composition
3 NO

Product documentation

View Indumarket specification summary (PDF)