A9F83232

Schneider Electric A9F83232 — Miniature Circuit Breaker 2P 32A B-Curve

Schneider Electric A9F83232 Miniature Circuit Breaker 2P 32A B-Curve. The Schneider Electric A9F83232 is a high-performance Acti9 iC60H Miniature Circuit Breaker (MCB), engineered for reliable protection in final distribution circuits. This 2-pole, 32A MCB features a B-curve thermal-magnetic trip unit, designed to safeguard electrical installations against overcurrents and short circuits. It offers significant breaking capacities, including 10000 A Icn at 400 V AC conforming to EN/IEC 60898-1 and 15 KA Icu at 380-415 V AC conforming to EN/IEC 60947-2, making it robust for demanding environments. Compatible with both AC (from 12V to 440V, including common 220-240V and 380-415V networks at 50/60 Hz) and DC networks up to 125V, it provides versatile application. Designed for 35 mm DIN rail mounting, its compact 36 mm width fits efficiently into modular enclosures. This Schneider Electric MCB is ideal for critical applications across Egypt and the Gulf, including industrial facilities like cement plants, oil and gas installations, water treatment plants, food and beverage processing, textile factories, and various commercial and building services.

Details

Related Schneider Electric parts

Request a quote for A9F83232

Specifications

Curve code
B
Net weight
0.25 Kg
Network type
DC; AC
Limitation class
3 conforming to EN/IEC 60898-1
Mounting support
35 mm DIN rail
Poles description
2P
[In] rated current
32 A
Trip unit technology
Thermal-magnetic
Dimensions (H x W x D)
85 Mm x 36 Mm x 78.5 Mm
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Manufacturer part number
A9F83232
Suitability for isolation
Yes conforming to EN/IEC 60947-2; Yes conforming to EN/IEC 60898-1
[Ue] rated operational voltage AC
12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz
[Ue] rated operational voltage DC
<= 125 V DC
Breaking capacity (IEC/EN 60898-1)
10000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
15 KA Icu at 380...415 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)