A9F79140

Schneider Electric A9F79140 — Miniature Circuit Breaker

Schneider Electric A9F79140 Acti9 iC60N Miniature Circuit Breaker 1P 40A C Curve. Discover the reliable Schneider Electric A9F79140 Acti9 iC60N Miniature Circuit Breaker, engineered for robust protection in final distribution circuits. This 1-pole (1P) MCB is rated at 40A with a C-curve tripping characteristic, ensuring dependable thermal-magnetic protection against overcurrents and short circuits. It offers significant breaking capacities, including 6000A (IEC/EN 60898-1) at 230V AC and 10kA (IEC/EN 60947-2) at 220-240V AC, making it ideal for various AC and DC networks operating at 50/60 Hz. Designed for ease of installation, the A9F79140 clips securely onto a 35 mm DIN rail and features an IP20 degree of protection. Its suitability for isolation, contact position indicator, and wide operating temperature range (-35 to 70 °C) highlight its versatility and safety features. This Schneider Electric MCB is perfectly suited for diverse applications across Egypt and the Gulf, including building services, residential installations, light industrial facilities, and sectors such as water treatment, food and beverage, and textiles. For a competitive quote on the Schneider Electric A9F79140, please submit your request today.

Details

Related Schneider Electric parts

Request a quote for A9F79140

Specifications

Width
18 Mm
Curve code
C
Net weight
0.215 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Device short name
iC60N
Network frequency
50/60 Hz
Poles description
1P
[In] rated current
40 A
Trip unit technology
Thermal-magnetic
IP degree of protection
IP20
Magnetic tripping limit
8 x In +/- 20 %
Manufacturer part number
A9F79140
Number of protected poles
1
Product or component type
Miniature circuit-breaker
Suitability for isolation
Yes
[Ue] rated operational voltage
220...240 V AC 50/60 Hz
Connections - terminals (rigid)
Single terminal (top or bottom) , for 1 cable(s) , 1…35 mm², rigid, copper
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 220...240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)