A9F75104

Schneider Electric A9F75104 — Miniature Circuit Breaker

Schneider Electric A9F75104 Miniature Circuit Breaker Acti9 iC60N 1P 4A D-Curve. Ensure robust electrical protection with the Schneider Electric A9F75104 Miniature Circuit Breaker from the Acti9 iC60N series. This essential 1-pole, 4A, D-curve MCB provides reliable thermal-magnetic protection against overcurrents and short-circuits in both AC and DC networks. Designed for versatility, it supports a wide operational voltage range from 12V to 240V AC and 12V to 72V DC, making it suitable for diverse applications. The A9F75104 boasts a breaking capacity of 6000A Icn at 230V AC (IEC/EN 60898-1) and 50KA Icu at 220-240V AC (IEC/EN 60947-2), along with excellent suitability for isolation. Its compact DIN-rail mountable design (85 x 18 x 78.5 mm) with IP20 protection (IP40 in modular enclosure) allows for easy integration into control panels and distribution boards. This Schneider Electric MCB is ideal for final distribution circuits across various demanding industries in Egypt and the Gulf, including cement plants, oil and gas facilities, water treatment stations, food and beverage production, and large-scale building services, providing crucial safety and operational continuity. Connection terminals accept rigid cables up to 25mm² and flexible cables up to 16mm². For reliable power distribution protection, request a quote today.

Details

Related Schneider Electric parts

Request a quote for A9F75104

Specifications

Curve code
D
Net weight
0.215 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Poles description
1P
Dimensions (HxWxD)
85 mm x 18 mm x 78.5 mm
[In] rated current
4 A
Trip unit technology
Thermal-magnetic
Mechanical durability
20000 Cycles
Connections - terminals
1...25 mm² rigid, 1...16 mm² flexible
IP degree of protection
IP20 (IP40 in modular enclosure)
Manufacturer part number
A9F75104
Product or component type
Miniature circuit-breaker
Suitability for isolation
Yes
Rated operational voltage (AC)
12...240 V AC 50/60 Hz
Rated operational voltage (DC)
12...72 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
50 KA Icu at 220...240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)