A9F75102

Schneider Electric A9F75102 — Miniature Circuit Breaker

Schneider Electric A9F75102 Miniature Circuit Breaker (MCB) Acti9 iC60N 1P 2A D-Curve. The Schneider Electric A9F75102 Acti9 iC60N Miniature Circuit Breaker (MCB) is a robust 1-pole, 2 Amp, D-curve device engineered for effective overcurrent protection in various distribution applications. Equipped with a thermal-magnetic trip unit, it ensures reliable safeguarding against short circuits and overloads in both AC (50/60 Hz) and DC networks, supporting operational voltages up to 240V AC and 72V DC. This MCB boasts impressive breaking capacities, including 6000A (IEC/EN 60898-1) at 230V AC and 50kA Icu (IEC/EN 60947-2) at 220-240V AC, making it highly suitable for demanding industrial environments. It features 35mm DIN rail mounting, IP20 protection (IP40 in modular enclosures), and a wide operating temperature range of -35…70 °C, ensuring performance in harsh conditions. The A9F75102 is an ideal choice for critical applications across Egypt and the Gulf, including motor control circuits in oil and gas, building services, water treatment, cement production, food and beverage, and textile industries, where robust, reliable electrical protection is paramount. Its compact 18mm width and suitability for isolation further enhance its versatility.

Details

Related Schneider Electric parts

Request a quote for A9F75102

Specifications

Width
18 Mm
Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
D
Net weight
0.215 Kg
Network type
DC, AC
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
1P
Tightening torque
2 N.M top or bottom
[In] rated current
2 A
Overvoltage category
IV
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
Connections - terminals
Single terminal (top or bottom), for 1 cable(s): 1-25 mm² rigid copper; 1-16 mm² flexible copper; 1-16 mm² flexible with ferrule copper
IP degree of protection
IP20, IP40 in modular enclosure
Manufacturer part number
A9F75102
Number of protected poles
1
Suitability for isolation
Yes
Rated operational voltage [Ue]
12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V DC, 60...72 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
50 KA Icu at 220-240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)