A9F74125

Schneider Electric A9F74125 — Miniature Circuit Breaker

Schneider Electric A9F74125 Acti9 iC60N Miniature Circuit Breaker 1P 25A C-Curve. The Schneider Electric A9F74125 is a robust Acti9 iC60N Miniature Circuit Breaker designed for reliable overcurrent protection in final distribution circuits. This 1-pole (1P) device has a rated current of 25 A and features a C-curve trip unit, providing thermal-magnetic protection against overload and short-circuit faults. It offers excellent breaking capacities, including 6000 A conforming to IEC/EN 60898-1 and 10 kA conforming to IEC/EN 60947-2 at 220-240 V AC. Compatible with both AC and DC networks, it supports a wide range of operational voltages from 12 V AC/DC up to 240 V AC, specifically catering to the 220-240 V AC 50/60 Hz standards prevalent in Egypt and the Gulf region. The A9F74125 is suitable for isolation and designed for easy clip-on mounting on a 35 mm DIN rail. Its compact 18 mm width makes it ideal for space-constrained panels. This dependable Schneider Electric MCB is essential for safeguarding electrical installations in diverse applications such as building services, water treatment facilities, food and beverage processing, and textile manufacturing.

Details

Related Schneider Electric parts

Request a quote for A9F74125

Specifications

Depth
78.5 Mm
Width
18 Mm
Height
85 Mm
Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
C
Net weight
0.215 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Device short name
IC60N
Poles description
1P
Tightening torque
2 N.M top or bottom
[In] rated current
25 A
Trip unit technology
Thermal-magnetic
Connections - terminals
Single terminal (top or bottom), rigid 1...25 mm², flexible 1...16 mm²
IP degree of protection
IP20
Manufacturer part number
A9F74125
Number of protected poles
1
Suitability for isolation
Yes
[Ue] rated operational voltage
12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V DC, 60...72 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 220...240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)