EZC250N3200

Schneider Electric EZC250N3200 — Moulded Case Circuit Breaker

Schneider Electric EZC250N3200 Easypact EZC250N 3-pole 200 A moulded case circuit breaker 25 kA. The Schneider Electric EZC250N3200 is a genuine Easypact EZC250N moulded case circuit breaker, 3-pole with all three poles protected and a fixed TM-D thermal-magnetic trip unit rated 200 A at 50 °C on a 250 A frame. Built to EN/IEC 60947-2, EZC250N3200 offers an ultimate breaking capacity Icu of 25 kA at 400/415 V AC 50/60 Hz, Ics of 12.5 kA, 690 V AC rated insulation voltage and 6 kV impulse withstand, matching the 400/415 V 50 Hz networks used across Egypt and the GCC. It gives overload and short-circuit protection, is suitable for isolation, and mounts fixed on a backplate with IP20 protection in a 165 x 105 x 60 mm body. It is used for main distribution board incomers, large pump and blower feeders in water and wastewater treatment, motor control centre incomers in cement plants, and process distribution in food and beverage and oil and gas sites.

Details

Related Schneider Electric parts

Request a quote for EZC250N3200

Specifications

Poles
3P, 3 protected poles (3d)
Standards
EN/IEC 60947-1, EN/IEC 60947-2
Trip unit
TM-D, thermal-magnetic
Mounting mode
Fixed, backplate; front upside and downside connection
Protection type
Overload protection, short-circuit protection
Connection pitch
35 mm
Network frequency
50/60 Hz
Utilisation category
Category A
Electrical durability
Category A: 5000 cycles at 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
10000 cycles
Trip unit rating (Ir)
200 A at 50 °C
Dimensions (H x W x D)
165 x 105 x 60 mm
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
EZC250N3200
Suitability for isolation
Yes conforming to IEC 60947-2
[In] rated current (frame)
250 A at 40 °C
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage
550 V AC 50/60 Hz conforming to IEC 60947-2; 250 V DC conforming to IEC 60947-2
Ambient air temperature for operation
-25…70 °C
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Breaking capacity (Icu) at 400/415 V AC 50/60 Hz
25 kA conforming to IEC 60947-2
[Ics] rated service breaking capacity at 400/415 V AC 50/60 Hz
12.5 kA conforming to IEC 60947-2

Product documentation

View manufacturer document (PDF)