A9F84313

Schneider Electric A9F84313 — Miniature Circuit Breaker

Schneider Electric A9F84313 iC60H Miniature Circuit Breaker 3P 13A C-Curve. The Schneider Electric A9F84313 is a robust Acti9 iC60H miniature circuit breaker (MCB) designed for reliable protection in final distribution circuits. This 3-pole, 13A, C-curve thermal-magnetic MCB provides essential overload and short-circuit protection for both AC and DC networks. It boasts a breaking capacity of 10000A Icn at 400V AC (conforming to EN/IEC 60898-1) and 15kA Icu at 380-415V AC (conforming to EN/IEC 60947-2), ensuring high performance under fault conditions. With wide operational voltage compatibility, including 380-415V AC, and 50/60 Hz network frequency, it is ideally suited for the diverse electrical standards across Egypt and the Gulf region. Featuring easy clip-on 35mm DIN rail mounting, a compact 54mm width, and IP20 protection, this MCB is a versatile choice for industrial control panels and building services. It finds typical applications in critical infrastructure sectors such as cement, oil and gas, water treatment, food and beverage, and textile industries, where dependable circuit protection is paramount. Its suitability for isolation further enhances safety.

Details

Related Schneider Electric parts

Request a quote for A9F84313

Specifications

Depth
78.5 Mm
Width
54 Mm
Height
85 Mm
Curve code
C
Net weight
0.375 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Device short name
iC60H
Network frequency
50/60 Hz
Poles description
3P
Tightening torque
2 N.M top or bottom
[In] rated current
13 A
Trip unit technology
Thermal-magnetic
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F84313
Product or component type
Miniature circuit-breaker
Suitability for isolation
Yes conforming to EN/IEC 60947-2, Yes conforming to EN/IEC 60898-1
[Ue] rated operational voltage
12...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, <= 180 V DC
Breaking capacity (IEC/EN 60898-1)
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Breaking capacity (IEC/EN 60947-2)
15 KA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)