Schneider Electric A9F84403 Miniature Circuit Breaker Acti9 iC60H 4P 3A C-Curve. The Schneider Electric A9F84403 Acti9 iC60H Miniature Circuit Breaker offers reliable and robust protection for final distribution circuits in demanding electrical installations across Egypt and the Gulf. This 4-pole (4P) device is rated for a 3 Ampere (3A) current and features a C-curve thermal-magnetic trip unit, ensuring effective overload and short-circuit protection for both AC and DC networks. Compatible with a wide range of operational voltages, including the prevalent 380-415 V AC 50/60 Hz systems, it boasts an impressive breaking capacity of 70 kA Icu conforming to EN/IEC 60947-2 and 10000 A Icn conforming to EN/IEC 60898-1. The A9F84403 is designed for 35 mm DIN rail mounting, offers excellent suitability for isolation, and has an IP20 degree of protection, making it suitable for various environments. Its broad operating temperature range of -35…70 °C and suitability for isolation further enhance its versatility. This essential component is well-suited for applications in industries such as cement, oil and gas, water treatment, food and beverage, textiles, and general building services.

Details

Related Schneider Electric parts

Request a quote for A9F84403

Specifications

Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
C
Net weight
0.5 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Poles description
4P
Tightening torque
2 N.M top or bottom
[In] rated current
3 A
Trip unit technology
Thermal-magnetic
Dimensions (H x W x D)
85 Mm x 72 Mm x 78.5 Mm
Connections - terminals
Single terminal (top or bottom), for 1 cable(s), 1…25 mm² rigid, copper; Single terminal (top or bottom), for 1 cable(s), 1…16 mm², flexible, copper
IP degree of protection
IP20 conforming to IEC 60529 (IP40 in modular enclosure (Insulation class II) conforming to IEC 60529)
Manufacturer part number
A9F84403
Suitability for isolation
Yes
[Ue] rated operational voltage
12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 250 V DC
Breaking capacity (IEC/EN 60898-1)
10000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
70 KA Icu at 380...415 V AC 50/60 Hz; 15 KA Icu at <= 250 V DC
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)