A9F84204

Schneider Electric A9F84204 — Acti9 iC60H Miniature Circuit Breaker

Schneider Electric A9F84204 Acti9 iC60H Miniature Circuit Breaker. The Schneider Electric A9F84204 Acti9 iC60H Miniature Circuit Breaker (MCB) is a robust and essential component for safeguarding electrical circuits against overcurrents and short circuits in diverse applications. This 2P, 4A, C-curve, thermal-magnetic MCB ensures reliable protection for both AC and DC networks operating at 50/60 Hz. It boasts impressive breaking capacities of 10 kA (IEC/EN 60898-1) at 400 V AC and 70 kA (IEC/EN 60947-2) at 380-415 V AC, making it suitable for demanding industrial environments. Designed for DIN-rail mounting, it offers easy installation and is rated for operation across a wide range of voltages, including 220-240 V AC and 380-415 V AC common in Egypt and the Gulf, as well as up to 125 V DC. With an IP20 degree of protection and high mechanical and electrical durability, this Schneider Electric A9F84204 MCB is ideal for critical final distribution circuits found in cement plants, oil and gas facilities, water treatment, food and beverage processing, textile factories, and various building services.

Details

Related Schneider Electric parts

Request a quote for A9F84204

Specifications

Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
C
Net weight
0.25 Kg
Network type
AC, DC
Product name
Acti9 iC60
Mounting support
35 mm DIN rail
Device short name
iC60H
Network frequency
50/60 Hz
Poles description
2P
[In] rated current
4 A
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
IP degree of protection
IP20, IP40 in modular enclosure
Manufacturer part number
A9F84204
Number of protected poles
2
Suitability for isolation
Yes
Rated operational voltage (AC)
12...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz
Rated operational voltage (DC)
<= 125 V DC
Breaking capacity (IEC/EN 60898-1)
10000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
70 KA Icu at 380...415 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)