A9F77150

Schneider Electric A9F77150 — Miniature Circuit Breaker

Schneider Electric A9F77150 Acti9 iC60N Miniature Circuit Breaker (MCB) 1P 50A C-curve. The Schneider Electric A9F77150 is a robust Acti9 iC60N Miniature Circuit Breaker (MCB) engineered for reliable protection in final distribution circuits. This 1-pole, 50A MCB features a C-curve trip characteristic, making it ideal for general-purpose applications where moderate inrush currents are expected. It offers impressive breaking capacities of 6000A (IEC/EN 60898-1 at 230V AC) and 10kA (IEC/EN 60947-2 at 220-240V AC), alongside comprehensive DC voltage compatibility up to 72V. Designed for universal 50/60 Hz networks, the A9F77150 ensures suitability for both AC and DC installations. Its thermal-magnetic trip unit provides dependable overload and short-circuit protection, while DIN rail mounting simplifies installation in industrial and commercial panels. With an IP20 rating and durable mechanical/electrical lifespans of 20,000 and 10,000 cycles respectively, this MCB is built to last. It is perfectly suited for building services, water treatment facilities, and light industrial applications across Egypt and the Gulf region, offering essential safety and operational continuity. For more information or to place an order, please request a quote.

Details

Related Schneider Electric parts

Request a quote for A9F77150

Specifications

Depth
78.5 Mm
Width
18 Mm
Height
85 Mm
Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
C
Net weight
0.215 Kg
Network type
DC, AC
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
1P
[In] rated current
50 A
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
Connections - terminals
Single terminal (top or bottom), for 1 cable(s), 1…35 mm², rigid, copper
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F77150
Number of protected poles
1
Suitability for isolation
Yes conforming to EN/IEC 60898-1, Yes conforming to EN/IEC 60947-2
[Ue] rated operational voltage
12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V DC, 60...72 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 230 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 220...240 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)