A9F74116

Schneider Electric A9F74116 — Miniature Circuit Breaker

Schneider Electric A9F74116 Acti9 iC60N 1-pole 16 A C-curve miniature circuit breaker. The Schneider Electric A9F74116 is an Acti9 iC60N miniature circuit breaker with one protected pole, a 16 A rated current and a C tripping curve. This thermal-magnetic MCB protects final distribution circuits against overload and short-circuit currents, offering 6000 A Icn at 230 V AC to EN/IEC 60898-1 and 10 kA Icu at 220...240 V AC to EN/IEC 60947-2, with magnetic tripping at 8 x In +/- 20 % and suitability for isolation under both standards. The A9F74116 clips onto 35 mm DIN rail, occupies two 9 mm pitches for an 18 mm width, accepts up to 25 mm2 rigid copper conductors at 2 N.m and is rated IP20 for operation from -35 to 70 degrees C. A 16 A C curve is the everyday choice for lighting and socket circuits, small pumps, instrument panels and control supplies in building services, water treatment, food and beverage plants, cement works and hotel facilities across Egypt and the Gulf.

Details

Related Schneider Electric parts

Request a quote for A9F74116

Specifications

Range
Acti9
Standards
EN/IEC 60898-1, EN/IEC 60947-2
Curve code
C
Net weight
0.215 kg
9 mm pitches
2
Product name
Acti9 iC60
Mounting mode
Clip-on, 35 mm DIN rail
Limitation class
3 conforming to EN/IEC 60898-1
Breaking capacity
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1; 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Device short name
iC60N
Network frequency
50/60 Hz
Poles description
1P
Tightening torque
2 N.m top or bottom
[In] rated current
16 A
Trip unit technology
Thermal-magnetic
Dimensions (H x W x D)
85 mm x 18 mm x 78.5 mm
Connections - terminals
1...25 mm2 rigid copper; 1...16 mm2 flexible copper
IP degree of protection
IP20 conforming to IEC 60529
Magnetic tripping limit
8 x In +/- 20 %
Manufacturer part number
A9F74116
Number of protected poles
1
Suitability for isolation
Yes conforming to EN/IEC 60898-1 and EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage
220...240 V AC 50/60 Hz (also 12...60 V AC, 100...133 V AC, 12...60 V DC, 60...72 V DC)
Mechanical / electrical durability
20000 cycles / 10000 cycles
Ambient air temperature for operation
-35...70 degrees C
[Ics] rated service breaking capacity
7.5 kA (75 % x Icu) at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2

Product documentation

View manufacturer document (PDF)