A9F74320

Schneider Electric A9F74320 — Miniature Circuit Breaker

Schneider Electric A9F74320 Acti9 iC60N 3-pole 20 A C-curve miniature circuit breaker. The Schneider Electric A9F74320 is a three-pole Acti9 iC60N miniature circuit breaker rated 20 A with a C tripping curve, built for 380...415 V three-phase final distribution. Its thermal-magnetic trip unit gives overload and short-circuit protection with 6000 A Icn at 400 V AC to EN/IEC 60898-1 and 10 kA Icu at 380...415 V AC to EN/IEC 60947-2, magnetic tripping at 8 x In +/- 20 %, current limitation class 3 and full suitability for isolation. The A9F74320 clips onto 35 mm DIN rail, is 54 mm wide across six 9 mm pitches, takes up to 25 mm2 rigid copper at 2 N.m, and works from -35 to 70 degrees C at IP20. A 20 A C curve on three phases suits small motor feeders, pump and fan starters, packaging lines and HVAC circuits found in water treatment, food and beverage, cement and oil and gas facilities in Egypt and the GCC.

Details

Related Schneider Electric parts

Request a quote for A9F74320

Specifications

Range
Acti9
Standards
EN/IEC 60898-1, EN/IEC 60947-2
Curve code
C
Net weight
0.375 kg
9 mm pitches
6
Product name
Acti9 iC60
Mounting mode
Clip-on, 35 mm DIN rail
Limitation class
3 conforming to EN/IEC 60898-1
Breaking capacity
6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1; 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Device short name
iC60N
Network frequency
50/60 Hz
Poles description
3P
Tightening torque
2 N.m top or bottom
[In] rated current
20 A
Trip unit technology
Thermal-magnetic
Dimensions (H x W x D)
85 mm x 54 mm x 78.5 mm
Connections - terminals
1...25 mm2 rigid copper; 1...16 mm2 flexible copper
IP degree of protection
IP20 conforming to IEC 60529
Magnetic tripping limit
8 x In +/- 20 %
Manufacturer part number
A9F74320
Number of protected poles
3
Suitability for isolation
Yes conforming to EN/IEC 60898-1 and EN/IEC 60947-2
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage
380...415 V AC 50/60 Hz (also 12...133 V AC, 220...240 V AC, 440 V AC, <= 180 V DC)
Mechanical / electrical durability
20000 cycles / 10000 cycles
Ambient air temperature for operation
-35...70 degrees C
[Ics] rated service breaking capacity
7.5 kA (75 % x Icu) at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2

Product documentation

View manufacturer document (PDF)