EZC250N3225

Schneider Electric EZC250N3225 — Circuit breaker

Schneider Electric EZC250N3225 EasyPact EZC250N Thermal-magnetic Circuit Breaker 225A 3P. The Schneider Electric EasyPact EZC250N Thermal-magnetic Circuit Breaker, part number EZC250N3225, is a robust and essential component for reliable electrical distribution in diverse industrial and commercial settings. This 3-pole circuit breaker, rated at 225 A at 40 °C, provides both overload and short-circuit protection, ideal for safeguarding critical infrastructure. Designed for both AC (50/60 Hz up to 550 V) and DC (up to 250 V) networks, it offers impressive breaking capacities, including 25 kA Icu at 380 V AC and 400-415 V AC. Its fixed mounting and front connections simplify installation into existing distribution boards. Key applications for the EZC250N3225 in the Egypt and Gulf regions span various industries, from power distribution in commercial buildings and data centers to heavy industrial use in cement plants, oil and gas facilities, water treatment stations, and food and beverage processing. It also finds use in textile manufacturing and general building services, ensuring continuous and safe operation. With its Category A utilisation and IP20 degree of protection, this Schneider Electric circuit breaker delivers consistent performance and safety in demanding environments.

Details

Related Schneider Electric parts

Request a quote for EZC250N3225

Specifications

Depth
60 Mm
Width
105 Mm
Height
165 Mm
Network type
DC, AC
Mounting mode
Fixed
Device short name
Easypact EZC250N
Network frequency
50/60 Hz
Poles description
3P
[In] rated current
225 A at 40 °C
Trip unit technology
Thermal-magnetic
Utilisation category
Category A
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
EZC250N3225
Suitability for isolation
Yes conforming to IEC 60947-2
Protected poles description
3t
[Ue] rated operational voltage
550 V AC 50/60 Hz, 250 V DC
Breaking capacity (Icu) at 380 V AC
25 KA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity (Icu) at 440 V AC
20 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Ambient air temperature for operation
-25…70 °C
Breaking capacity (Icu) at 400...415 V AC
25 KA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity at 380 V AC
12.5 KA at 380 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity at 400/415 V AC
12.5 KA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

Product documentation

View manufacturer document (PDF)