EZC100H2015

Schneider Electric EZC100H2015 — Circuit breaker

Schneider Electric EZC100H2015 EasyPact EZC100H circuit breaker 15A 2P. The Schneider Electric EZC100H2015 is a robust and reliable EasyPact EZC100H moulded case circuit breaker, designed for efficient electrical distribution in a wide range of industrial and commercial applications. This 2-pole, 15A thermal-magnetic circuit breaker provides essential overload and short-circuit protection for both AC and DC networks, operating seamlessly across a 50/60 Hz frequency. With impressive breaking capacities, including 50 KA Icu at 220/240 V AC and 30 KA Icu at 400/415 V AC, it ensures dependable performance and enhanced safety for critical infrastructure. Its fixed mounting and toggle control offer straightforward integration and operation. Ideal for distribution boards, the Schneider Electric EZC100H2015 is a common choice in the demanding environments of Egypt and the Gulf region, including sectors like cement production, oil and gas, water treatment, food and beverage, and building services. Its IP20 degree of protection and operational temperature range of -25 to 70 °C further enhance its suitability for challenging conditions.

Details

Related Schneider Electric parts

Request a quote for EZC100H2015

Specifications

Depth
60 Mm
Width
50 Mm
Height
130 Mm
Network type
AC, DC
Mounting mode
Fixed
Protection type
Overload protection, Short-circuit protection
Network frequency
50/60 Hz
Poles description
2P
[In] rated current
15 A at 40 °C
Trip unit technology
Thermal-magnetic
Breaking capacity code
H
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
EZC100H2015
Suitability for isolation
Yes conforming to IEC 60947-2
Protected poles description
2t
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage
550 V AC 50/60 Hz conforming to IEC 60947-2, 250 V DC conforming to IEC 60947-2
Ambient air temperature for operation
-25…70 °C
Breaking capacity Icu at 220...240 V AC
50 KA conforming to IEC 60947-2
Breaking capacity Icu at 400...415 V AC
30 KA conforming to IEC 60947-2
[Ics] rated service breaking capacity at 400/415 V AC
7.5 KA conforming to IEC 60947-2
[Ics] rated service breaking capacity at 220/230/240 V AC
25 KA conforming to IEC 60947-2

Product documentation

View manufacturer document (PDF)