Schneider Electric EZC250H4150 — Circuit breaker

Schneider Electric EZC250H4150 EasyPact EZC250H circuit breaker, TMD, 150A, 4 poles 3d. The Schneider Electric part number EZC250H4150 is a robust EasyPact EZC250H circuit breaker, meticulously engineered for dependable protection within electrical distribution boards. This 4-pole device, featuring 3 protected poles (3t), offers a substantial rated current of 150 A at 40 °C, making it a versatile solution for numerous applications. Equipped with a thermal-magnetic trip unit, it delivers essential overload and short-circuit protection across both AC and DC networks operating at 50/60 Hz. Key breaking capacities include 36 KA Icu at 380-415 V AC and 85 KA Icu at 220-240 V AC, alongside 30 KA Icu at 250 V DC. Designed for straightforward installation with fixed mounting and toggle control, the EZC250H4150 ensures ease of use. Its IP20 degree of protection and an operational temperature range of -25 to 70 °C guarantee durability in diverse environments. This Schneider Electric EZC250H4150 circuit breaker is an excellent choice for critical infrastructure across Egypt and the Gulf, including cement plants, oil and gas facilities, water treatment plants, food and beverage manufacturing, textiles, and general building services. For reliable electrical system safeguarding, request a quote for the Schneider Electric EZC250H4150 today.

Details

Related Schneider Electric parts

Request a quote for EZC250H4150

Specifications

Control type
Toggle
Network type
DC, AC
Mounting mode
Fixed
Protection type
Overload protection, Short-circuit protection
Network frequency
50/60 Hz
Poles description
4P
[In] rated current
150 A at 40 °C
Trip unit technology
Thermal-magnetic
Mechanical durability
10000 Cycles
Height x Width x Depth
165 x 140 x 60 Mm
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
EZC250H4150
Suitability for isolation
Yes conforming to IEC 60947-2
Breaking capacity Icu (AC)
36 KA at 380...415 V AC 50/60 Hz, 85 KA at 220...240 V AC 50/60 Hz
Breaking capacity Icu (DC)
30 KA at 250 V DC 2P
Protected poles description
3t
[Ue] rated operational voltage
550 V AC 50/60 Hz, 250 V DC
Ambient air temperature for operation
-25…70 °C

Product documentation

View manufacturer document (PDF)