A9F77410

Schneider Electric A9F77410 — Miniature Circuit Breaker

Schneider Electric A9F77410 Miniature circuit breaker (MCB), Acti9 iC60N, 4P, 10A, C curve. The Schneider Electric A9F77410 Acti9 iC60N Miniature Circuit Breaker (MCB) provides reliable protection for final distribution circuits. This 4-pole, 10A device features a C-curve thermal-magnetic trip unit, safeguarding against overcurrents and short circuits in both AC and DC networks. It is compatible with a wide range of operational voltages, including 220-240 V AC, 380-415 V AC, and up to 250 V DC, making it highly suitable for electrical installations across Egypt and the Gulf. Key specifications include a breaking capacity of 10 kA (Icu) at 380-415 V AC and 6000 A (Icn) at 400 V AC. Designed for 35mm DIN rail mounting, the A9F77410 offers suitability for isolation and an IP20 degree of protection. This robust Schneider Electric component is ideal for critical infrastructure in industries such as cement, oil and gas, water treatment, food and beverage, textiles, and general building services.

Details

Related Schneider Electric parts

Request a quote for A9F77410

Specifications

Curve code
C
Net weight
0.5 Kg
Network type
AC; DC
Product name
Acti9 iC60N
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
4P
[In] rated current
10 A
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
Breaking capacity (Icn)
6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Breaking capacity (Icu)
10 KA Icu at 380-415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Connections - terminals
Single terminal (top or bottom), for 1 cable(s), 1…25 mm² rigid, copper; Single terminal (top or bottom), for 1 cable(s), 1…16 mm² flexible, copper
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F77410
Product or component type
Miniature circuit-breaker
Suitability for isolation
Yes
[Ue] rated operational voltage
220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; <= 250 V DC
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)