A9F75416

Schneider Electric A9F75416 — Miniature Circuit Breaker

Schneider Electric A9F75416 Acti9 iC60N Miniature Circuit Breaker (MCB) 4P 16A D-Curve. The Schneider Electric A9F75416 is a robust Acti9 iC60N Miniature Circuit Breaker (MCB) designed for reliable protection in final distribution circuits. This 4-pole, 16 A device features a D-curve trip unit with thermal-magnetic technology, ensuring precise overload and short-circuit protection for various electrical installations. Compatible with both AC and DC networks, it supports a wide range of operational voltages, including the prevalent 220-240 V AC and 380-415 V AC found across Egypt and the Gulf region, alongside up to 250 V DC applications. It offers a substantial breaking capacity of 10 kA Icu at 380-415 V AC (conforming to EN/IEC 60947-2) and 6000 A Icn at 400 V AC (conforming to EN/IEC 60898-1). The A9F75416 is suitable for isolation and features DIN rail mounting for easy installation, with an IP20 degree of protection. Its robust design is ideal for demanding environments common in industrial sectors such as cement production, oil and gas, water treatment plants, food and beverage manufacturing, textiles, and commercial building services. For detailed technical information or to request a quotation, please contact us.

Details

Related Schneider Electric parts

Request a quote for A9F75416

Specifications

Depth
78.5 Mm
Width
72 Mm
Height
85 Mm
Standards
EN/IEC 60947-2, EN/IEC 60898-1
Curve code
D
Net weight
0.5 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Network frequency
50/60 Hz
Poles description
4P
[In] rated current
16 A
Trip unit technology
Thermal-magnetic
Electrical durability
10000 Cycles
Mechanical durability
20000 Cycles
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F75416
Suitability for isolation
Yes
[Ue] rated operational voltage
12...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, <= 250 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 380...415 V AC 50/60 Hz, 10 KA Icu at <= 250 V DC
Ambient air temperature for operation
-35…70 °C

Product documentation