Schneider Electric A9F73406 Acti9 iC60N Miniature Circuit Breaker (MCB) 4P 6A B-curve. The Schneider Electric A9F73406 is a robust Acti9 iC60N Miniature Circuit Breaker (MCB) designed for reliable protection in final distribution circuits. This 4-pole device provides a rated current of 6 A with a B tripping curve, utilizing thermal-magnetic technology for effective overload and short-circuit protection. It is highly versatile, supporting both AC networks up to 440 V (including 380-415 V AC 50/60 Hz) and DC networks up to 250 V. Key breaking capacities include 10 kA Icu at 380-415 V AC and 6000 A Icn at 400 V AC conforming to IEC standards. Engineered for DIN-rail mounting, the A9F73406 is an ideal choice for diverse applications across Egypt and the Gulf, including critical building services, water treatment plants, oil and gas facilities, cement factories, and food and beverage processing. Its IP20 protection and wide operating temperature range (-35…70 °C) ensure dependable performance in demanding environments. For precise technical details and to secure this essential Schneider Electric component, please request a quote.

Details

Related Schneider Electric parts

Request a quote for A9F73406

Specifications

Depth
78.5 Mm
Width
72 Mm
Height
85 Mm
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Curve code
B
Net weight
0.5 Kg
Network type
AC; DC
Mounting support
35 mm DIN rail
Device short name
IC60N
Poles description
4P
[In] rated current
6 A
Trip unit technology
Thermal-magnetic
Breaking capacity (DC)
10 KA Icu at <= 250 V DC
IP degree of protection
IP20 conforming to IEC 60529
Manufacturer part number
A9F73406
Number of protected poles
4
Product or component type
Miniature circuit-breaker
Suitability for isolation
Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
Terminal capacity (rigid)
1…25 mm²
Terminal capacity (flexible)
1…16 mm²
[Ue] rated operational voltage
12...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 380...415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 250 V DC
Breaking capacity (IEC/EN 60898-1)
6000 A Icn at 400 V AC 50/60 Hz
Breaking capacity (IEC/EN 60947-2)
10 KA Icu at 380...415 V AC 50/60 Hz
Ambient air temperature for operation
-35…70 °C

Product documentation