Schneider Electric LC1D40004G6 CTR;AC Control;AC Coil. For operating rates until 3600 cycles/hour and environments until 60°C, it procures reliability and durability to standard applications. Very compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EN). Official Schneider characteristics include Range of product: TeSys Deca; Product or component type: Contactor; Device short name: LC1D; Contactor application: Resistive load; Utilisation category: AC-1 AC-3 AC-3e AC-4; Poles description: 4P; [Ue] rated operational voltage: Power circuit: 690 V AC 25...400 Hz; [Ie] rated operational current: 60 A (at <60 °C) at 440 V AC AC-1 for power circuit.
10 A gG for control circuit conforming to IEC 60947-5-1 80 A at 690 V coordination type 1 for power circuit 80 A at 690 V coordination type 2 for power circuit
Rated breaking capacity
800 kA at 440 V for power circuit conforming to IEC 60947
Manufacturer part number
LC1D40004G6
Pole contact composition
4 NO
Product or component type
Contactor
Irms rated making capacity
140 A AC for control circuit conforming to IEC 60947-5-1 800 A at 440 V AC for power circuit conforming to IEC 60947
[Uc] control circuit voltage
120 V AC 60 Hz
[Ie] rated operational current
60 A (at <60 °C) at 440 V AC AC-1 for power circuit
[Ue] rated operational voltage
Power circuit: 690 V AC 25...400 Hz
[Ith] conventional free air thermal current
10 A (at 60 °C) for control circuit 40 A (at 60 °C) for power circuit