Schneider Electric LC1D258BD TeSys D Contactor, 4P, 24 V DC coil. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. It provides a 24V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). Official Schneider characteristics include Range of product: TeSys Deca; Product or component type: Contactor; Device short name: LC1D; Contactor application: Resistive load; Utilisation category: AC-1; Poles description: 4P; [Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; [Ie] rated operational current: 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit.
450 A at 440 V for power circuit conforming to IEC 60947
Manufacturer part number
LC1D258BD
Pole contact composition
2 NO + 2 NC
Product or component type
Contactor
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 450 A at 440 V for power circuit conforming to IEC 60947
[Uc] control circuit voltage
24 V DC
[Ie] rated operational current
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Icw] rated short-time withstand current
240 A 40 °C - 10 s for power circuit 380 A 40 °C - 1 s for power circuit 50 A 40 °C - 10 min for power circuit 120 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit 40 A (at 60 °C) for power circuit