LC1D099G7

Schneider Electric LC1D099G7 — CTR;AC Control

Schneider Electric LC1D099G7 CTR;AC Control. For operating rates until 3600 cycles/hour and environments until 60°C, it procures reliability and durability to standard applications. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EN). Official Schneider characteristics include Range of product: TeSys Deca; Product or component type: Contactor; Device short name: LC1D; Contactor application: Resistive load Motor control; Utilisation category: AC-1 AC-4 AC-3 AC-3e; Poles description: 3P; [Ue] rated operational voltage: Power circuit: Power circuit: <= 300 V DC;

Details

Related Schneider Electric parts

Request a quote for LC1D099G7

Specifications

Motor power hp
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
Motor power kW
2.2 kW at 220...230 V AC 50/60 Hz (AC-3) 4 kW at 380...400 V AC 50/60 Hz (AC-3) 4 kW at 415...440 V AC 50/60 Hz (AC-3) 5.5 kW at 500 V AC 50/60 Hz (AC-3) 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) 2.2 kW at 400 V AC 50/60 Hz (AC-4) 2.2 kW at 220...230 V AC 50/60 Hz (AC-3e) 4 kW at 380...400 V AC 50/60 Hz (AC-3e) 4 kW at 415...440 V AC 50/60 Hz (AC-3e) 5.5 kW at 500 V AC 50/60 Hz (AC-3e) 5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Protective cover
With
Range of product
TeSys Deca
Device short name
LC1D
Poles description
3P
Compatibility code
LC1D
Utilisation category
AC-1 AC-4 AC-3 AC-3e
Contactor application
Resistive load Motor control
Manufacturer part number
LC1D099G7
Pole contact composition
3 NO
Product or component type
Contactor
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
[Uc] control circuit voltage
120 V AC 50/60 Hz
[Ue] rated operational voltage
Power circuit: Power circuit: <= 300 V DC
[Ith] conventional free air thermal current
25 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit

Product documentation

View Indumarket specification summary (PDF)