A9F78406

Schneider Electric A9F78406 — Miniature Circuit Breaker

Schneider Electric A9F78406 Miniature circuit breaker, Acti9 iC60N, 4P, 6A, B curve. The Schneider Electric A9F78406 Miniature Circuit Breaker (MCB) from the Acti9 iC60N series is engineered for robust and reliable protection in diverse electrical distribution systems. This 4-pole, 6A thermal-magnetic MCB with a B tripping curve provides essential overcurrent and short-circuit protection for both AC and DC networks. Designed for universal application, it supports operational voltages up to 440 V AC and 250 V DC, with a breaking capacity of 6000 A (IEC/EN 60898-1) at 400 V AC and 10 kA (IEC/EN 60947-2) at 380-415 V AC. Its DIN-rail mountable design and IP20 (IP40 in enclosure) protection make it suitable for a wide range of industrial and commercial settings. The A9F78406 ensures suitability for isolation, enhancing safety during maintenance. This versatile MCB is ideal for critical final distribution circuits in the challenging environments of Egypt and the Gulf, including applications in water treatment plants, building services, light industrial facilities, and commercial complexes, providing dependable performance in ambient temperatures from -35°C to 70°C. For reliable circuit protection, request a quote for the Schneider Electric A9F78406 today.

Details

Related Schneider Electric parts

Request a quote for A9F78406

Specifications

Depth
78.5 Mm
Width
72 Mm
Height
85 Mm
Curve code
B
Net weight
0.5 Kg
Network type
AC, DC
Mounting support
35 mm DIN rail
Breaking capacity
36 KA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2, 20 KA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10 KA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 6 KA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10 KA Icu at <= 250 V DC conforming to EN/IEC 60947-2, 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Poles description
4P
Tightening torque
2 N.M top or bottom
[In] rated current
6 A
Trip unit technology
Thermal-magnetic
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper; Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal a
IP degree of protection
IP20 conforming to IEC 60529, IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Manufacturer part number
A9F78406
Suitability for isolation
Yes conforming to EN/IEC 60898-1, Yes conforming to EN/IEC 60947-2
[Ue] rated operational voltage
12...133 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, <= 250 V DC
Ambient air temperature for operation
-35…70 °C

Product documentation

View manufacturer document (PDF)